Calibrarea unei Pumps PIUSI Cube 56

Pumps PIUSI Cube 56 / 70 / 90 are reliable solutions for the distribution of fuel in non-commercial and industrial applications. To ensure precise measurements and optimal operation, it is essential to perform periodically calibration of the meter. This procedure corrects any measurement errors caused by wear or changes in conditions of use.

Why is calibration important?

  1. Precision in fuel distribution – Any downturn can lead to financial losses or to erroneous reports.
  2. Compliance with regulations – In some cases, it is necessary to comply with the standards of accuracy imposed by the authorities.
  3. Long-term maintenance – Regular calibration prolongs the life of the equipment.

Equipment and equipment required for calibration

  • Certificate measuring container (e.g. a calibration vessel).
  • Fuel for testing.
  • Keys and screws to access the calibration mechanism.
  • Manualul de utilizare al pompei PIUSI Cube 56.

Pașii for calibrarea pompei PIUSI Cube 56

1. Preparation of equipment

  • Make sure the pump is shut down and all connections are secure.
  • Clean the work area to avoid contamination of the fuel.

2. Accessing the calibration mechanism

  • Open the pump cap to access the mechanical counter.
  • Identify the adjustment screw or calibration button according to the manual.

3. Conducting an initial test

  • It distributes a fixed amount of fuel into a calibration vessel (e.g. 10 litres).
  • Note the value indicated by the pump counter and compare it to the actual volume of the container.

4. Adjusting the counter

  • Where there is a difference between the volume indicated and the actual volume:
    • For positive errors (counter indicates more than the actual volume): rotate the adjustment screw in the direction of clocks.
    • For negative errors (the counter indicates less than the actual volume): rotates the screw in the reverse direction of clocks.
  • Set gradually and test again, until the errors are removed.

5. Final verification

  • Repeat the test process 2-3 times to ensure that the measurements are constant and correct.
  • Put the pump cap back on hold and assemble all the screws in order to secure the heat.

Useful advice for efficient calibration

  • Calibration should be performed at medium temperatures in order to avoid the influence of thermal dilation of fuel.
  • Always use a certified calibration container to get correct measurements.
  • If large errors occur or the meter cannot be adjusted, consult an authorised technician or contact the manufacturer.

Când trebuie calibrată Pump PIUSI Cube 56?

  1. Periodic – Depending on the volume distributed, calibration is recommended every 6-12 months.
  2. After replacement of the components – Any change in the distribution system may affect the measurements.
  3. In case of manifest error – If you notice large deviations during normal use.

Proper calibration of the PIUSI Cube 56 pump is essential for efficiency and accuracy. Compliance with the above instructions will help you to maintain the optimal performance of the equipment. If you encounter difficulties, our team is here to help you!

Contact us for technical support, spare parts or if you want to perform a calibration by our specialized team.